Envoy Installation, Commissioning & Operating Manual
Technical Data Continued
SUITABILITY (RECOMMENDED EQUIPMENT)
Conventional: Twin-Wire:
Smoke / Heat Detectors
Nittan: Evolution Range
UB-4SD schottky diode base
Apollo: Series 65
45681-201 schottky diode base
Apollo: Series 65
45681-206 base
Hochiki: CDX Range
YBN-R-6SK schottky diode base
Hochiki: CDX Range
YBO-R-6PA base
Call Point
KAC:
MCP1A-R-470, 470 OHM Resistor
KAC:
MCP1B-R-TW, Polarised & 470 OHM
Sounders Use polarised and suppressed, light
current 24vdc electronic sounders or
bells (Fulleon, Besson etc.)
Use polarised and suppressed, light
current 24vdc electronic sounders or
bells (Fulleon, Besson etc.)
Fulleon:
CXL-U-R-BB, 470 OHM Resistor
Fulleon:
CX-G-R-TW, Polarised & 470 OHM
Detector Zones:
Voltage 17 – 28V dc. Quiescent current 3.5mA each. End of line value 4K7 Ohm.
Schottky diode or zener clamp detector removal monitoring.
Sounder
Circuits:
17 – 28V dc reverse polarity monitored. Sounders must be polarised and
suppressed. End of line value 4K7 Ohm. Output current 500mA. Maximum shared
sounder load 1.0 amp.
Fuses:
Mains: F2AH, 250VAC, 20mm HBC Ceramic. Compliant with IEC (EN 60127 A2)
Battery: 1 amp, nanofuse, fast acting
Supply: 1 amp, nanofuse, fast acting
Sounders: 500mA, nanofuse, fast acting